GAS BURNERS MODULATING LOW NOX GAS X5/MCE-LX-EL
TECHNICAL DATA GAS X5/MCE-LX-EL
MODEL GAS X5/MCE-LX-EL
Thermal power min. 1°st. / min. 2°st. – max. 2° st.60/130-300 Mcal/h
Thermal power min. 1°st. / min. 2°st. – max. 2° 69.8/151-349kW
Gas flow G20 (NATURAL GAS) min. 1°st. / min. 2°st. – max. 2° 7/15.2-35Nm³/h
Fuel: Natural gas (second family)
Fuel category: I2R,I2H,I2L,I2E,I2E+,I2Er,I2ELL,I2E(R)B
NOx <80: class 3 (EN 676)mg/kWh
Intermittent working operation (min. 1 STOP every 24 hours) modulating
Environmental conditions operation/storage: -15…+40°C / -20…+70°C, rel. humidity max. 80%
Max temperature combustion air 60°C
Minimum pressure gas train D1″-S NATURAL GAS 31 mbar
Minimum pressure gas train D1″1/4-S NATURAL GAS 21 mbar
Minimum pressure gas train D1″1/2-S NATURAL GAS 18 mbar
Maximum pressure at the entry of the valves (Pe.max) 360 mbar
Nominal electric power 540 W
Fan motor 370 W
Nominal absorption 2.4 A
Power supply: 1/N~230V-50Hz
Degree of electric protection: IP 40
Noisiness min-max 66-71 dB(A)
Weight burner 35 kg
DETAILED SPECIFICATION
Gas burner modulating (PID fully modulating) with optional modulation kit and probe, low emissions certified in
conformity with CE 676 class 3 (NOx < 80 mg/kWh–CO < 60 mg/kWh), composed by:
- Die-cast aluminum body;
- Fan at high pressurisation;
- Combustion head with adjustment at high performance and elevated flame stability equipped with inox steel blast tube and
steel flame disc;
- Combustible-air adjustment for optimal combustion value;
- Protection cover with noise reduction plate;
- Flange and insulating gasket for fixing at generator;
- Electronic control system for controlling and command the burner;
- Single-phase power supply;
- Safety air pressure switch to stop the burner in case of failed or anomalous fan operation;
- Spherical gas servocontrolled valve: progressive start and free way passage with total opening;
- Servomotor for air shutter;
- Servomotor for spherical gas valve;
- Mobile shutter with total closure when idle for minimize the energetic losses related at boiler cooling;
- Gas train complete of: one-block valve class A (1st stage slow opening + safety), minimum gas pressure switch and stabiliser
Hubungi Kami
PT. SUMBER TEKNIK INDUSTRI
Jl. Mangga Pesona Lebak Wangi 2 blok A3 no 15 Kec, Sepatan Timur Kab, tangerang Provinsi Banten 15521
Phone : 021 3529 5862
Mobile : 0852 82762 784
Email : idmslamet@gmail.com
Website : https://boilersburner.com
Refferensi: https://www.fbr.it/media/4550/d-1/t-file/SK073037_LX_C_en.pdf
Comments
No comment yet.