FBR GAS X4/MCE TWO STAGE MODULATING
GAS BURNERS TWO STAGES PROGRESSIVE OR MODULATING
TECHNICAL DATA BURNERS FBR GAS X4/MCE
Thermal power min. 1°st. / min. 2°st. – max. 2°st. 40/100-200Mcal/h
Thermal power min. 1°st. / min. 2°st. – max. 2°st. 46/116-232 kW
Gas flow G20 (NATURAL GAS) min. 1°st. / min. 2°st. – max. 2°4.6/11.6-23.2 Nm³/h]
Fuel: NATURAL GAS (second family) – L.P.G. (third family) 1.8/4.5-9 Nm³/h
Fuel category: I2R,I2H,I2L,I2E,I2E+,I2Er,I2ELL, I2E(R)B/I3B/P,I3+,I3P,I3B,I3R
Intermitted working operation (min. 1 stop every 24 hours) two stages progressive or modulating
Environmental conditions operation / storage: -15…+40°C / -20…+70°C, umidità rel. max. 80%
Max. temperature combustion air 60[°C]
Minimum pressure gas train D3/4″-S NATURAL GAS/L.P.G. -/- mbar
Minimum pressure gas train D1″-S NATURAL GAS/L.P.G. 14/21 mbar
Minimum pressure gas train D1″1/4-S NATURAL GAS/L.P.G. 11/19 mbar
Minimum pressure gas train D1″1/2-S NATURAL GAS/L.P.G. 8/17 mbar
Maximum pressure at the entry of valves (Pe. max) 360[mbar]
Nominal electric power 226 W
Fan motor 200 W
Nominal current absorption 1.1A
Power supply: 1N~230V – 50Hz
Electric protection degree: IP 40
Noisiness *** min. – max. 66-71 dBA
Burner weight 17[kg]
DETAILED SPECIFICATION
- Protection cover with noise reduction plate;
- Flange and insulating gasket for fixing at boiler;
- Single phase power supply;
- Safety air pressure switch to stop the burner in lock-out in case of failed or anomalous fan operation;
- Gas train completely assembled and tested; complete of one-block valve A class (1st stage slow opening + safety), minimum gas
pressure switch and filter stabilizer;
- Ionisation probe for flame detection;
- IP 40 electric protection level;
- Spherical gas valve servo-controlled; progressive start and free way passage with total opening;
- Servomotor for air shutter and for the spherical gas valve;
- Set up for the additional specific kit that transforms burner operation as modulating i.e. the modulating kit allows to supply any
Hubungi Kami
PT. SUMBER TEKNIK INDUSTRI
Jl. Mangga Pesona Lebak Wangi 2 blok A3 no 15 Kec, Sepatan Timur Kab, tangerang Provinsi Banten 15521
Phone : 021 3529 5862
Mobile : 0852 82762 784
Email : idmslamet@gmail.com
Website : https://boilersburner.com
Refferensi: https://www.fbr.it/media/4439/d-1/t-file/SK073030_en.pdf
Comments
No comment yet.