BURNER RIELLO LIGHT OIL (TWO STAGE)RL 100

RIELLO RL 100 TWO STAGE 12345

BURNER RIELLO LIGHT OIL (TWO STAGE)RL 100

RIELLO LIGHT OIL TWO STAGE RL 100 356/711 ÷ 1186 kW

TECHNICAL DATA MODEL : RL 100 TYPE : 661 T1
OUTPUT DELIVERY (1) 2nd stage : 711 – 1186 kW , 612 – 1020 Mcal/h , 60 – 100 kg/h
OUTPUT DELIVERY (1) 1st stage : 356 – 711 kW , 306 – 612 Mcal/h , 30 – 60 kg/h
FUEL : LIGHT OIL/SOLAR
– Net calorific value : 11.8 kWh/kg, 10,2 (10.200 kcal/kg),
– Density : 0.82 – 0.85 kg/dm
– Viscosity at 20 °C mm2/s max 6 (1,5 °E – 6 cSt)
OPERATION – Intermittent (min. 1 stop in 24 hours).
– Two-stage (high and low flame) and single-stage (all – nothing).
NOZZLES number 2
STANDARD APPLICATIONS Boilers: water, steam, diathermic oil
AMBIENT TEMPERATURE : °C 0 – 40

COMBUSTION AIR TEMPERATURE : °C max 60
PUMP delivery (at 20 bar) kg/h 220
pressure range bar : 10 – 20
fuel temperature : ° C max 60
ELECTRICAL PROTECTION : IP 44

ELECTRICAL DATA
Motor IE1
POWER SUPPLY – V: 230 – 400 with neutral ~ +/- 10%, Hz: 50 – three-phase
ELECTRICAL MOTOR – rpm: 2860, kW: 1,5, V: 230/400, A: 6.4/3.7
IGNITION TRASFORMER – V1 – V2: 230 V – 2 x 5 kV, I1 – I2: 1.9 A – 30 mA
ELECTRICAL POWER CONSUMPTION – kW max: 2.6
Motor IE2
POWER SUPPLY – V: 230 – 400 with neutral ~ +/- 10%, Hz: 50 – three-phase
ELECTRICAL MOTOR – rpm: 2860, kW: 1,5, V: 230/400, A: 5.5/3.4
IGNITION TRASFORMER – V1 – V2: 230 V – 2 x 5 kV, I1 – I2: 1.9 A – 30 mA
ELECTRICAL POWER CONSUMPTION – kW max: 2.5

 

RIELLO LIGHT OIL TWO STAGE RL 130 486/948 ÷ 1540 kW

TECHNICAL DATA MODEL : RL 130 TYPE : 662 T1

OUTPUT DELIVERY (1) 2nd stage : 948 – 1540 kW , 816 – 1325 Mcal/h , 80 – 130 kg/h
OUTPUT DELIVERY (1) 1st stage : 486 – 948 kW , 418 – 816 Mcal/h , 41 – 80 kg/h
FUEL : LIGHT OIL/SOLAR
Net calorific value : 11.8 kWh/kg, 10,2 (10.200 kcal/kg),
Density : 0.82 – 0.85 kg/dm
Viscosity at 20 °C mm2/s max 6 (1,5 °E – 6 cSt)
OPERATION – Intermittent (min. 1 stop in 24 hours).
Two-stage (high and low flame) and single-stage (all – nothing).
NOZZLES number 2
STANDARD APPLICATIONS Boilers: water, steam, diathermic oil

AMBIENT TEMPERATURE : °C 0 – 40
COMBUSTION AIR TEMPERATURE : °C max 60
PUMP delivery (at 20 bar) kg/h 220
pressure range bar : 10 – 20
fuel temperature : ° C max 60
ELECTRICAL PROTECTION : IP 44
NOISE LEVELS (2) : dBA 78.5

ELECTRICAL DATA
Motor IE1
POWER SUPPLY – V: 230 – 400 with neutral ~ +/- 10%, Hz: 50 – three-phase
ELECTRICAL MOTOR – rpm: 2860, kW: 2,2, V: 230/400, A: 8.5/4.9
IGNITION TRASFORMER – V1 – V2: 230 V – 2 x 5 kV, I1 – I2: 1.9 A – 30 mA
ELECTRICAL POWER CONSUMPTION – kW max: 3.2
Motor IE2
POWER SUPPLY – V: 230 – 400 with neutral ~ +/- 10%, Hz: 50 – three-phase
ELECTRICAL MOTOR – rpm: 2860, kW: 2,2, V: 230/400, A: 7.9/4.6
IGNITION TRASFORMER – V1 – V2: 230 V – 2 x 5 kV, I1 – I2: 1.9 A – 30 mA
ELECTRICAL POWER CONSUMPTION – kW max: 3.1

 

Hubungi Kami

PT. SUMBER TEKNIK INDUSTRI

Jl. Mangga Pesona Lebak Wangi 2 blok A3 no 15 Kec, Sepatan Timur Kab, tangerang Provinsi Banten 15521

Phone       : 021 3529 5862

Mobile      : 0852 82762 784

Email        : idmslamet@gmail.com

Website    : https://boilersburner.com

Cataloge   : https://www.rielloburners.co.uk/images/content/downloads/RL.pdf